The internal resistance of drastically undersized wiring may not be capable of passing sufficient current to overload the household breaker
Yeah. If you undersized a en entire houses ring circuit at AWG24, then indeed a 30A fuse wouldn’t be tripped. Though on the plus side, to even achieve it you would need to undersize the wire to such a massive degree that the wire itself just becomes a fuse.
In a our real world overhere, of fucking course a ring circuit can pass enough current to trip it’s breaker, and it’s fucking laughable to claim they can’t.
Here again, you’re demonstrating my exact point, despite claiming that what I am saying is “completely untrue”: The rest of the world builds its appliances to tolerate at least that 16A fault. For the UK to use that exact same manner of protection, they would need to build their appliances to tolerate a 30A fault. The same appliance would need a much heavier power cord in the UK than in the EU.
No they don’t. They can actually use much smaller power cords. Because there’s a fuse in the plug itself. If the plug itself has 1A fuse, then no matter what happens, the maximum amount of current the device can ever consume is 1A, so 1A is the highest fault current that device will ever have to handle. The UK system actually makes fault protection on the device side much better and easiest.







The higher voltage has nothing whatsoever to do with ring circuits. The UK runs on the same 220-240V AC as all of mainland Europe. And Africa. And most of mainland Asia. And South America. And Oceania. And most of the middle east. So not quite “higher than any other country”
Also those two claims are diametrically opposed to each other. Unless UK people use over twice the amount of electricity than Americans, the higher voltage will lead to LOWER total current. That’s quite literally the specific and sole motivating factor behind choosing a higher grid voltage.
And the current a conductor can pass has nothing whatsoever to do with it’s safety. You could have 50 amps blowing through a circuit, if it’s at 12V you can still touch it without getting a shock. Your car battery is capable of peak currents of several HUNDRED amps, and those are considered safe enough to just carry around by random people with bare hands…
The Japanese plugs are basically the same as American. You can literally get an electric shock if you hold them wrong whilst unplugging. There’s exposed live contacts from when you start unplugging until the prongs break their connection to the outlet.
Basically everything you said is demonstrably false. I’ve rarely seen someone be this confident and this incorrect about something.
That is utterly irrelevant. Circuit breakers and fuses are designed for the exclusive and sole purpose of protecting the circuit from being overloaded. A 100 amp circuit with a 100 Amp fuse is exactly as safe as a 20 amp circuit with a 20 amp fuse or a 5 amp circuit with a 5 amp fuse. If the voltage is above ~100-200V, all 3 of these are hundreds of times the amount of current it would take to deliver a fatal electric shock, and none of those fuses would trip from you getting shocked.
And a dead short on a 240V network will literally trip everything. UK ring circuits are fused at 30 Amps. A dead short at 240V with only the internal resistance of copper wiring would pull current in the neighborhood of 1000 amps. 1000, somewhat famously, being slightly larger than 30, making this another lie there.
And even if it weren’t a lie, how on earth does the location of the fuse make a difference in safety here ? If it’s in the wall or in the plug, as long as it’s there and does it’s job both would be equally safe.
No it isn’t. 110V is still dangerous to a child, and if you think otherwise I hope to god you aren’t, or ever become a parent. Also, as I stated, your plugs literally allow for an electric shock to happen whilst unplugging them because they’re so terrible. As for whole house GFCI, that is by necessity included in a ring circuit that wants GFCI on any outlet at all.
Also you seem to fundamentally misunderstand the relationship of current and voltage. For a given electrical appliance, with a given wattage, a lower voltage means it needs to draw more current, not less. That’s why the US Japan need to have 20A household breakers, whereas in the EU 16A branches are more than enough, whilst still providing a higher load handling capability than a 20A Japanese fuse. A 1000 Watt microwave plugged into a Japanese socket will draw over twice as much current as a 1000 Watt microwave plugged into an EU or UK socket (which also means it produces 4 times the amount of electrical waste energy as heat, though that is generally negligible for short household cable runs either way. Can make a difference on the scale of a country though).
For a given voltage, the outcome of recieving a shock on a 20A fused circuit is literally indistinguishable and fully identical to that of receiving a shock on a 100A fused circuit. Identical. Literally.
No it isn’t. I literally just told you you can buy 15A rated extension cords in Japan in the comment you’re replying to. 15, is in fact less than 20, just fyi.
Wrong. Again. The current limit imposed by the internal resistance of your body at voltages in the range of 100-200 is a few hundred milliamps. Maybe an amp or two if you stick electrodes inside yourself, and anything higher than 100 mA going through your heart is already lethal anyway. You’re gonna be dead 200 times over waiting for your 20A fuse to save you. The power that will pass through your body depends exclusively and solely on the voltage. The capacity and fusing of the circuit is utterly irrelevant, unless it’s fused at like 40 MILLI amps.
ANY cable being driven above it’s rated load is a fire hazard. There are healthy margins in those ratings, so going slightly over is likely not going to have any affect, but those margins are for good reason (namely people like you thinking it’s fine to plug a 15A cable into a 20A circuit without external fusing or current limiting), and deliberately overloading any part of an electric circuit is ALWAYS dangerous and stupid.
And what about 7A cables you can get in japan ? you can explicitly get 0.75mm² cables, which are only rated to 7Amps. Just as confident of blasting 20A through those ? Almost 9 times the amount of waste heat being generated in the core than at it’s max rated load.
Your device could slowly be melting itself into a pile of burning plastic, as long as it’s drawing less than 16 Amps to do so, the breakers will not trip. As I’ve pointed outñ
And in fact, the fused plugs actually make it way MORE likely for something to trip on a device side fault in the UK, because the current only has to be like 3Amps to kill the fuse. In every other place of the world, current needs to be at least 16A before anything trips.
I address that point, quite literally, in a later a paraph where I write
So what happened here ? Did you not read my comment ? Did you not understand it ? Or did you read it understand, and then continue to pretend like I haven’t already explicitly addressed this anyway ?
Here’s a list of prior arguments I’ve made, that you fully ignored. Until.you give me s good faith really to THE ENTIRETY of each argument,. I’m ignoring you.